* MAIN POWER : 3PH, AC 220/380/400/415/440/460/480 V, 50/60Hz (+10%)
* MOTOR : TENV, External Cooling Pin, Insulation Class: F, Thermostat,
* REMOTE MONITORING SWITCH : Standard-8EA (S1-S8, LATCH, AC250V 2A), Other-1EA (FAULT, 1C)
* INDICATION ON LOCAL CONTROL PANEL : Graphic LCD, 4-LED (Power, Fault, Close, Open)
* TERMINAL : Double Sealing Structure with O-ring
-. CONTROL : 48 Contacts/M4 (Voltage rated : AC250V 5A)
-. POWER : 4 Contacts/M5 (Voltage rated : AC660V 63A)
* ENCLOSURE : IP68 (10m for 100hrs in water)
* SPACE HEATER : 10W, DC 24V
* OPERATIONAL TEMPERATURE : -20C ~ 70C
* MANUAL HAND-WHEEL : Top-mounted, directly connected to drive sleeve, switvhing lever (manual-electric) with automatic reset.
* CABLE ENTRY : 1 - PF1 1/2", 2- PF1"
* LOCAL CONTROL PANEL : Selector Switch for OPEN/CLOSE, Selector Switch for REMOTE/STOP/LOCAL
* STANDARD PAINTING : Liquified Paint